Web Server Interface 3-35
Message Size
Maximum number of characters to buffer before sending a frame.
Values: 01024
Default: 256
Idle Character Delay
Maximum number of idle character time to wait before sending a frame.
Values: 065535
Default: 10
Input Terminator
Decimal value of the character that terminates a message before sending a
frame.
Values: 0255
Default: 0
Data Direction
Data direction that the port will support. If set to “Input,” the port will only
accept incoming data and will not transmit data. If set to “Output,” the port
will ignore any incoming data. If set to “Both,” the port will process all data.
Values: Input, Output, Both
Default: Both
SCADA Loopback
Determines if and where SCADA will loopback received data.
Values: None, Loopback to Network, Loopback to Port
Default: None
The table below these parameters displays the SCADA statistics.
The SCADA Details screen provides the following user-activated buttons:
Figure 3.28
SCADA Device List Screen
Select the appropriate numbered link under the “Device column to access the
SCADA Device Details screen(Figure 3.29) where you can map SCADA
devices to endpoints.
Button Function
Submit Sets any values that have been changed.
SCADA Device List Displays a table that shows the mapping between
SCADA devices and endpoints (Figure 3.28).
Clear SCADA Statistics Clears all SCADA statistics.